Work out your steam cost per tonne and what passing valves, failed steam traps, bare insulation, excess blowdown and lost condensate cost your plant every year, in rupees. This is step one of our free steam audit: your estimate first, then our engineers measure it on site with ultrasonic and thermal imaging instruments.
A calculator can only work with what you already know. Most steam is lost in places nobody has listed: valves that look shut, traps that were never tagged, insulation that is wet under the cladding. Our free steam audit finds and measures those.
See what the audit adds ↓Quick estimate: enter counts, for example “6 traps blowing”. Good for plant owners and a first look.
Field survey: add each valve, trap and insulation item as you test it, with its tag, readings and verdict. Your entries are saved on this device as you go.
If the mill burns its own bagasse and bagasse is fully used, steam lost on the HP header (upstream of the turbine) is better valued as lost export power. Each loss is valued once, on one basis: never fuel and export added together.
Usually the most valuable finding. Check closed drain, vent, bypass and blowdown valves for a hot downstream pipe. One passing drain valve on an HP line can outweigh every trap in the plant.
Light (0.5 to 1 mm): downstream warm but under 100 °C, faint ultrasound. Moderate (1.5 to 2.5 mm): downstream hot within 1 m, clear continuous ultrasound. Blowing (3 to 5 mm): downstream near steam temperature for several metres, loud. Read body, then downstream at 1D, 3D and 10D. Where a double block and bleed exists, crack the bleed. Look first at HP drains, start-up vents, PRDS and turbine bypasses, blowdown valves, soot blower isolation, safety valves and manual bypasses around control valves. Never touch a bare surface on a live HP line.
Test every trap two ways. Ultrasonic on the body and 300 mm downstream: a working trap cycles; failed open gives continuous rushing flow; thermodynamic traps cycling faster than about 20 times a minute are worn. Temperature upstream and downstream: downstream near saturation means blowing through; below about 100 °C on a live line means blocked or air-bound. Visual where discharge is open: a continuous plume is failed open, slugs are normal. Codes: OK cycling, FO failed open, LK leaking, FC failed closed, OS out of service.
A bare valve body runs within 10 to 20 °C of the steam inside it. Wet insulation loses heat almost like bare metal and shows hot on a thermal camera.
Set IR emissivity to 0.95 for oxidised steel, rusted pipe and painted cladding. On bright aluminium cladding use the contact probe instead. Record surface temperature, size, count or length, ambient, and whether indoor or outdoor. Condition codes: B bare, D damaged or missing cladding, W wet, T thin or compressed. Count flange pairs by size on hot lines; they are easy to miss.
Needs steam generation from Step 1. Blowdown is worked out from a solids balance of feedwater and boiler water TDS.
Needs steam generation from Step 1. Every tonne of condensate returned saves the heat in it and a cubic metre of treated water.
| Finding | Loss | Value per year | Basis | Fix | Cost to fix (₹) | Payback |
|---|
Enter a cost to fix against each finding to see simple payback. Plants approve short paybacks first.
Steam loss through openings uses Napier’s orifice formula with a 0.75 discharge coefficient (kg/h = 0.4 × area in mm² × absolute pressure in bar). Heat loss from surfaces uses combined convection and radiation coefficients for still air, doubled outdoors. Steam properties from IAPWS-IF97. Boiler efficiency is on GCV basis. These are survey estimates; a site audit replaces them with measured findings.
Our free audit replaces each assumption above with a measured reading, a tag number and a photograph.
Book a free steam auditThe calculator gives you a number. The audit gives you the evidence behind it: every loss found on site, measured, tagged, photographed and priced, so your engineers can act on it and your management can approve it.
The survey is done while the plant is running, because traps and valve seats can only be tested with steam flowing. For sugar mills that means during the crushing season.
Our engineers follow your safety induction and work permit system and wear helmet, safety shoes, full sleeves, gloves and hearing protection. Hot surfaces on live HP lines are read from a safe distance and never touched, and nobody stands in line with a vent or drain discharge.